Ürün ayrıntıları:
|
Gerilim: | 0.6/ 1kv | zırhlama: | HAYIR |
---|---|---|---|
Yalıtım: | PVC | Çekirdek: | Çoklu Çekirdek |
Sıcaklık aralığı: | - 30 ℃ ila + 70 ℃ | kılıflı: | PVC |
This product is suitable for power transmission and distribution in lines with AC 50Hz and rated voltage not exceeding 0.6/1kV.
GB/T 12706.1,IEC 60502-1
CHARACTERISTIC
Specs |
Conductor diameter |
Nominal thickness of insulation |
Lining thickness |
Nominal thickness of steel wire |
Nominal thickness of sheath |
Approximate outer diameter of cable |
Approximate cable weight |
3×1.5 |
1.38 |
0.8 |
1 |
0.8 |
1.8 |
15.1 |
376 |
3×2.5 |
1.78 |
0.8 |
1 |
0.8 |
1.8 |
15.9 |
432 |
3×4 |
2.25 |
1 |
1 |
1.25 |
1.8 |
18.8 |
680 |
3×6 |
2.76 |
1 |
1 |
1.25 |
1.8 |
19.8 |
776 |
3×10 |
4 |
1 |
1 |
1.25 |
1.8 |
22.5 |
1009 |
3×16 |
5 |
1 |
1 |
1.25 |
1.8 |
24.6 |
1265 |
3×25 |
6.1 |
1.2 |
1 |
1.6 |
1.8 |
28.6 |
1855 |
3×35 |
7.2 |
1.2 |
1 |
1.6 |
1.8 |
31.2 |
2248 |
3×50 |
8.4 |
1.4 |
1 |
1.6 |
2 |
35.1 |
2835 |
3×70 |
10 |
1.4 |
1.2 |
2 |
2.1 |
40.2 |
3962 |
3×95 |
12 |
1.6 |
1.2 |
2 |
2.2 |
45.6 |
5070 |
3×120 |
13 |
1.6 |
1.2 |
2 |
2.3 |
47.9 |
5923 |
3×150 |
14.9 |
1.8 |
1.4 |
2.5 |
2.5 |
54.7 |
7676 |
3×185 |
16.5 |
2 |
1.4 |
2.5 |
2.7 |
59.5 |
9116 |
3×240 |
18.4 |
2.2 |
1.6 |
2.5 |
2.9 |
65.3 |
11289 |
3×300 |
21 |
2.4 |
1.6 |
2.5 |
3.1 |
72.2 |
13681 |
3×400 |
23.4 |
2.6 |
1.8 |
3.15 |
3.4 |
80.6 |
17764 |
Q. Where are SWA-PVC cables typically used?
A. Suitable for:
Underground direct burial (with drainage)
Industrial plants with mechanical stress
Hazardous environments (e.g., chemical exposure)
Q. How does steel wire armour enhance cable performance?
A. Mechanical protection: Resists crushing, rodent damage, and impact.
Grounding: Acts as an earth continuity conductor in some designs
Q. What are the temperature limits for SWA-PVC cables?
A. Operating range: -15°C to +70°C (PVC insulation)
Max conductor temperature: 70°C under continuous load
Q. Are SWA-PVC cables flame-retardant?
A. Standard versions comply with IEC 60332-1 (flame propagation test). For higher requirements, choose LSZH (Low Smoke Zero Halogen) variant
Q.. How to calculate bending radius during installation?
A. Minimum bending radius = 12× cable diameter to avoid armour deformation
Q.. Can SWA-PVC cables be installed in wet conditions?
A. Yes, provided the outer sheath is intact. For submerged use, ensure IP68-rated joints and anti-corrosion armour
Q. What standards apply to SWA-PVC cables?
A. International: IEC 60502-1
Regional: BS 5467 (UK), UL 4 (US)
İlgili kişi: Mr. Bai
Tel: +8619829885532